PRODUCTS

Take a look at our signature products of Switchgears

EPE provides a wide range of products and services for the generation, transmission and distribution sectors of the Electrical Power Industry, and is heavily involved in the manufacturing, engineering and project activities, and services for the power industry.

With an existing plant built on a 6 acres land area, EPE maintains its reputation and capability to undertake and complete its projects within the stipulated time. EPE has the potential to achieve a minimum of USD50 million sales annually on Electrical Distribution Products and Services. 

CERTIFICATION

Our products are certified as follows:

AIR INSULATED SWITCHGEAR (AIS)

Floor Mounted Withdrawable Type

AIS 12A20 / 25 with VFT-12 VCB

Full Spec AIS 12A20 / 25 with VFT-12 VCB

12A20 / 25 with VFT-12 VCB Full Spec

Switchgear Model Unit 12A20 12A25
Conformance IEC 60298, IEC 60694, IEC 62271-200
Rated voltage kV 12
Rated frequency Hz 50
Rated Insulation Level
Power frequency withstand voltage/min kV/1 min 28/32
Lightning impulse withstand voltage (peak) kV, 1.2/50µs 75/85
Rated normal current of Busbar A 800/1250/2000
Rated short time withstand current kA/3s 20 25
Rated peak withstand current kA 50 63
Standard degree of protection
Enclosure 4X
Compartment 3X
Dimension
Width mm 600, 800 (2000A)
Depth mm 2200, 2250 (with PT)
Height mm 2300
Circuit Breaker Model Unit VFT-12
Conformance IEC 62271-100
Rated voltage kV 12
Rated current A 630/1250/2000
Rated frequency Hz 50
Rated Insulation Level
Power frequency withstand voltage/min kV/1 min 28/32
Lightning impulse withstand voltage (peak) kV, 1.2/50µs 75/85
Rated short circuit breaking current kA, rms 20/25
Rated short circuit withstand current kA/3s 20/25
Rated short circuit making current (peak) kA 50/63
Rated short circuit making current (peak) kA 50/63
Electrical endurance 274 (Class E2)
Mechanical endurance 10,000 (Class M2)
Rated operating sequency/duty O-0.3s-CO-3min-CO
Rated closing time ms <60
Rated opening time ms <50
Rated breaking time ms <60
Standard trip/close supply Vdc 30/110
Standard motor charging supply Vdc (Vac) 30/110 (240Vac)

AIS 10D with 12D VCB

Full Spec 10D with VFT-12D VCB Full Spec​

10D with VFT-12D VCB Full Spec

Switchgear Model Unit 10D (Double Bus)
Conformance IEC 60298, IEC 60694
Rated voltage kV 12
Rated frequency Hz 50
Rated Insulation Level
Power frequency withstand voltage/min kV/1 min 28
Lightning impulse withstand voltage (peak) kV, 1.2/50µs 50
Rated normal current of Busbar A 800/1250/2000
Rated short time withstand current kA/3s 25
Rated peak withstand current kA 63
Standard degree of protection
Enclosure 4X
Compartment 3X
Dimension
Width mm 700
Depth mm 1950
Height mm 2400
Circuit Breaker Model Unit VFT-12
Conformance IEC 56
Rated voltage kV 12
Rated current A 630/1250/2000
Rated frequency Hz 50
Rated Insulation Level
Power frequency withstand voltage/min kV/1 min 28
Lightning impulse withstand voltage (peak) kV, 1.2/50µs 75
Rated short circuit breaking current kA, rms 25
Rated short circuit withstand current kA/3s 25
Rated short circuit making current (peak) kA 63
Rated operating sequency/duty O-0.3s-CO-3min-CO
Rated closing time ms <60
Rated opening time ms <50
Rated breaking time ms <60
Standard trip/close supply Vdc 30/110
Standard motor charging supply Vdc (Vac) 30/110 (240Vac)

AIS 24A25 with VJ 22 VCB

Full Spec AIS 24A25 with VJ 22 VCB

24A25 with VJ 22 VCB Full Spec

Switchgear Model Unit 24A25
Conformance IEC 60298, IEC 60694
Rated voltage kV 24
Rated frequency Hz 50
Rated Insulation Level
Power frequency withstand voltage/min kV/1 min 50
Lightning impulse withstand voltage (peak) kV, 1.2/50µs 125
Rated normal current of Busbar A 1250/2000
Rated short time withstand current kA/3s 25
Rated peak withstand current kA 62.5
Standard degree of protection
Enclosure 3X
Compartment 2X
Dimension
Width mm 900, 1100 (2000A)
Depth mm 3000, 3500 (with PT)
Height mm 2350
Circuit Breaker Model Unit VJ 22
Conformance IEC 56
Rated voltage kV 24
Rated current A 630/1250/2000
Rated frequency Hz 50
Rated Insulation Level
Power frequency withstand voltage/min kV/1 min 50
Lightning impulse withstand voltage (peak) kV, 1.2/50µs 125
Rated short circuit breaking current kA, rms 25
Rated short circuit withstand current kA/3s 25
Rated short circuit making current (peak) kA 62.5
Rated operating sequency/duty O-0.3s-CO-3min-CO
Rated closing time ms 50
Rated opening time ms 50
Rated breaking time ms 70
Standard trip/close supply Vdc 110
Standard motor charging supply Vdc (Vac) 110

AIS 36A25 with VJ 32D VCB

Full Spec AIS 36A25 with VJ 32D VCB

36A25 with VJ 32D VCB Full Spec

Switchgear Model Unit 36A25 (Single Bus) 36A25 (Double Bus)
Conformance IEC 60298, IEC 60694
Rated voltage kV 36
Rated frequency Hz 50
Rated Insulation Level
Power frequency withstand voltage/min kV/1 min 70
Lightning impulse withstand voltage (peak) kV, 1.2/50µs 170
Rated normal current of Busbar A 1250/2000
Rated short time withstand current kA/3s 25
Rated peak withstand current kA 62.5
Standard degree of protection
Enclosure 3X
Compartment 2X
Dimension
Width mm 1100
Depth mm 3650
Height mm 2150 2350
Circuit Breaker Model Unit VJ32 (Single Bus) VJ32D (Double Bus)
Conformance IEC 56
Rated voltage kV 36
Rated current A 800/1250/2000
Rated frequency Hz 50
Rated Insulation Level
Power frequency withstand voltage/min kV/1 min 70
Lightning impulse withstand voltage (peak) kV, 1.2/50µs 170
Rated short circuit breaking current kA, rms 25
Rated short circuit withstand current kA/3s 25
Rated short circuit making current (peak) kA 62.5
Rated operating sequency/duty O-0.3s-CO-3min-CO
Rated closing time ms 60
Rated opening time ms 50
Rated breaking time ms 70
Standard trip/close supply Vdc 30/110
Standard motor charging supply Vdc (Vac) 30/110 (240Vac)

Cassette Type

AIS 12kV AMS

Full Spec AIS 12kV AMS

12kV AMS with 12kV VEP VCB Full Spec

Switchgear Model Unit 12kV AMS
Conformance IEC 62271-200
Rated voltage kV 7.2/12/15/17.5
Rated frequency Hz 50/60
Rated Insulation Level
Power frequency withstand voltage/min kV/1 min 42
Lightning impulse withstand voltage (peak) kV, 1.2/50µs 75/95
Rated normal current of Busbar A 630/1250/1600/2000 2500/3150/4000
Rated short time withstand current kA/3s 20/25/31.5/40/50
Rated peak withstand current kA 50/63/80/125/130
Standard degree of protection
Enclosure 4X
Compartment 2X
Dimension
Width mm 650, 800, 1000
Depth mm 1400
Height mm 2250
Circuit Breaker Model Unit 12kV VEP
Conformance IEC 62271-100
Rated voltage kV 7.2/12/15/17.5
Rated current A 630/1250/1600/2000 2500/3150/4000
Rated frequency Hz 50/60
Rated Insulation Level
Power frequency withstand voltage/min kV/1 min 42
Lightning impulse withstand voltage (peak) kV, 1.2/50µs 75/95
Rated short circuit breaking current kA, rms 20/25/31.5/40/50
Rated short circuit withstand current kA/3s 20/25/31.5/40/50
Rated short circuit making current (peak) kA 50/63/80/125/130
Electrical endurance 274 (Class E2)
Mechanical endurance 10,000 (Class M2)
Rated operating sequency/duty O-0.3s-CO-3min-CO
Rated closing time ms 25-75
Rated opening time ms 25-35
Rated breaking time ms 40-50
Standard trip/close supply Vdc 110/220 (110/220Vac)
Standard motor charging supply Vdc (Vac) 110/220 (110/220Vac)

AIS 24kV AMS

Full Spec AIS 24kV AMS

24kV AMS 24kV VEP VCB Full Spec

Switchgear Model Unit 24kV AMS
Conformance IEC 62271-200
Rated voltage kV 24
Rated frequency Hz 50/60
Rated Insulation Level
Power frequency withstand voltage/min kV/1 min 50/65
Lightning impulse withstand voltage (peak) kV, 1.2/50µs 125
Rated normal current of Busbar A 630/1250/1600/2000 2500
Rated short time withstand current kA/3s 20/25/31.5
Rated peak withstand current kA 50/63/80
Standard degree of protection
Enclosure 4X
Compartment 2X
Dimension
Width mm 800 (1000)
Depth mm 1680
Height mm 2250
Circuit Breaker Model Unit 24kV VEP
Conformance IEC 62271-100
Rated voltage kV 24
Rated current A 630/1250/1600/2000 2500
Rated frequency Hz 50/60
Rated Insulation Level
Power frequency withstand voltage/min kV/1 min 50/65
Lightning impulse withstand voltage (peak) kV, 1.2/50µs 125
Rated short circuit breaking current kA, rms 20/25/31.5
Rated short circuit withstand current kA/3s 20/25/31.5
Rated short circuit making current (peak) kA 50/63/80
Electrical endurance 274 (Class E2)
Mechanical endurance 10,000 (Class M2)
Rated operating sequency/duty O-0.3s-CO-3min-CO
Rated closing time ms 50
Rated opening time ms 50
Rated breaking time ms 70
Standard trip/close supply Vdc 110/220 (110/220Vac)
Standard motor charging supply Vdc (Vac) 110/220 (110/220Vac)

AIS 40.5kV AMS

Full Spec AIS 40.5kV AMS

40.5kV AMS with 40.5kV VEP VCB or 40.5kV FEP GCB Full Spec

Switchgear Model Unit 40.5kV AMS
Conformance IEC 62271-200
Rated voltage kV 33/36/40.5
Rated frequency Hz 50/60
Rated Insulation Level
Power frequency withstand voltage/min kV/1 min 95
Lightning impulse withstand voltage (peak) kV, 1.2/50µs 185
Rated normal current of Busbar A 630/1250/1600/2000 2500/3150
Rated short time withstand current kA/3s 25/31.5
Rated peak withstand current kA 63/80
Standard degree of protection
Enclosure 4X
Compartment 2X
Dimension
Width mm 1200
Depth mm 2500
Height mm 2400
Circuit Breaker Model Unit 40.5 VEP (VCB) 40.5kV FEP (SF6 Gas CB)
Conformance IEC 62271-100 IEC 62271-100
Rated voltage kV 33/36/40.5 40.5
Rated current A 630/1250/1600/ 2000/2500/3150 630/1250/1600/ 2000/2500
Rated frequency Hz 50/60 50/60
Rated Insulation Level
Power frequency withstand voltage/min kV/1 min 95 95
Lightning impulse withstand voltage (peak) kV, 1.2/50µs 185 185
Rated short circuit breaking current kA, rms 25/31.5 25/31.5
Rated short circuit withstand current kA/3s 25/31.5 25/31.5
Rated short circuit making current (peak) kA 63/80 63/80
Electrical endurance 274 (Class E2) 274 (Class E2)
Mechanical endurance 10,000 (Class M2) 10,000 (Class M2)
Rated operating sequency/duty O-0.3s-CO-3min-CO O-0.3s-CO-3min-CO
Rated closing time ms 55-80
Rated opening time ms 25-40
Rated breaking time ms 60
Standard trip/close supply Vdc 110/220 (110/220Vac) 110/220 (110/220Vac)
Standard motor charging supply Vdc (Vac) 110/220 (110/220Vac) 110/220 (110/220Vac)
Annual leakage % N/A < 0.1%
SF6 rated pressure MPa N/A 0.35
SF6 alarm pressure MPa N/A 0.28

GAS INSULATED SWITCHGEAR (GIS)

BGA36 Single Bus Bar

BGA36 Double Bus Bar

Full Spec GIS BGA36

EPE Type BGA Compact Gas Insulated Switchgear Full Spec

Characteristics Unit 12kV 24kV 36kV
Configuration Single Busbar / Double Busbar
Rated voltage kV 12 24 36
Maximum operating voltage kV 12 24 36
Rated frequency Hz 50
Rated Insulation Level
Rated Power frequency withstand voltage/min kV/1 min 28 50 70
Rated lightning impulse withstand voltage kV, 1.2/50µs 75 125 170
Rated busbar current A 2000
Rated feeder current A 630/1250/2000
Rated short time withstand current kA/3s 25
Rated peak withstand current kA 63
Internal arc protection ALFR – 25kA, 1 sec
Insulating medium SF6
Rated pressure (gauge) MPa 0.08
Low pressure alarm stage – 1 MPa 0.06
Low pressure alarm stage – 2 MPa 0.05
High pressure MPa 0.12
Leakage rate % pa 0.1
Standard degree of protection
High voltage live parts IP 65
Low voltage compartment IP 4X
Ambient temperature – maximum value °C 40
Relative humidity, 24 average / 1 month average % 95/90
Standard altitude for erection above sea level m 1000
EPE Type DGA 3 Position Isolator
Operation of 3 position isolator Motorised / Manual
Auxiliary voltage
Control circuit Vdc 110
Motor circuit (Vac/Vdc) Vdc 110
EPE Type VGA Vacuum Circuit Breaker
Characteristics Unit 12kV 24kV 36kV
Rated voltage kV 12 24 36
Maximum operating voltage kV 12 24 36
Rated frequency Hz 50
Rated Power frequency withstand voltage/min kV/1 min 28 50 70
Rated lightning impulse withstand voltage kV, 1.2/50µs 75 125 170
Rated short circuit breaking current of circuit breaker kA 25
Rated short circuit making current of circuit breaker kA 63
Rated operating sequence O – 0.3 s – CO – 3 min – CO
Rated closing time msec 70 70 70
Rated opening time msec 50 50 50
Rated TRV for terminal fault / FPTC factor p.u. 1.5 1.5 1.5
Rate of rise kV/us 0.34 0.47 0.57
TRV peak voltage kV 20.6 41.2 61.7
Type of operating mechanism Motor charged spring stored energy
Tripping system Shunt trip
Spring charging motor Vdc 110
Output W 60
Current A 2 ~ 3
Closing coil auxiliary voltage Vdc 110
Current A 4
Tripping coil auxiliary voltage Vdc 110
Current A 5
Dimension
Unit Feeder Incomer Bus Section Riser Bus Coupler
Single Busbar
Height mm 2610 na
Depth mm 1580 na
Width (630A, 1250A) mm 700 na
Width (2000A) mm 800 800 800 700 na
Approx. weight per panel kg 1300 1450 1200 1000 na
Double Busbar
Height mm 2610
Depth mm 2405
Width (630A, 1250A) mm 700
Width (2000A) mm 800 800 800 700 800
Approx. weight per panel kg 1900 2100 1800 1600 1900

DISTRIBUTION TRANSFORMERS

L-Series Cast Resin Transformer

Full Spec L-Series Cast Resin Transformer

L-Series Cast Resin Transformer Full Spec

12kV, 500 – 2500kVA Distribution Transformer

Type Po (W) Pk (75°C) Pk (120°C) Uk % Io % Lp dB (A) Gt kg Dimensions (mm)
a b c d
EPE L-500/12 1140 4180 5500 4 1 50 2040 1450 850 1400 660
EPE L-1000/12 1730 6960 8800 6 0.6 50 3130 1650 1070 1630 820
EPE L-1250/12 2050 8290 10700 6 0.6 52 3550 1650 1070 1780 820
EPE L-1600/12 2400 10040 12500 6 0.6 52 4780 1770 1070 1965 820
EPE L-2000/12 3000 12370 16000 6 0.6 52 5690 1950 1070 2010 820
EPE L-2500/12 3530 14700 18500 6 0.6 52 6530 2080 1070 2010 820

36kV, 500 – 2500kVA Distribution Transformer

Type Po (W) Pk (75°C) Uk % Io % Lp dB (A) Gt kg Dimensions (mm)
a b c d
EPE L-500/33 1620 5810 6 1 50 2580 1860 850 1960 660
EPE L-1000/33 2430 9120 6 0.6 52 4320 221 1070 2110 820
EPE L-1250/33 2830 11110 6 0.6 52 4835 2300 1070 2070 820
EPE L-1600/33 3240 13520 6 0.6 52 5580 2470 1070 2170 820
EPE L-2000/33 3820 15920 6 0.4 52 8000 2490 1070 2440 820
EPE L-2500/33 4450 19070 6 0.4 52 8690 2780 1370 2275 1070

Oil Immersed Transformer

Full Spec Oil Immersed Transformer

Oil Immersed Transformer Full Spec

Parameter Technical Specification
Oil Immersed Distribution Transformer Hermitically sealed (without conservator) or with conservator
Rated power 25 – 3150kVA
Insulation level According to IEC Um = 1.1, 3.6, 7.2, 12, 17.5, 24, 36kV According to ANSI up to 36.5kV
Phases 3-phase (single phase is available on request)
Tappings ±2.5% or ±2x2.5% (or different ranges on request)
Voltage regulation With off circuit tap changer (Regulation with on-load tap changer is available on request)
Rated secondary voltage From 220 to 800V
Short circuit impedance Uk = 4% for P≤630kVA and Um≤24kV Uk = 4% or 4.5% for P≤630kVA and Um≤36kV Uk = 6% for P>630kVA
Rated frequency 50Hz (60Hz on request)
Vector groups Yzn recommended up to 50kVA and Um≤24kV Yzn recommended up to 100kVA with Um=36kV Dyn for all other rated power (any vector group according to IEC Standards)
Material thermal class insulation According to IEC 60085 class A
Temperature rise Mean winding temperature rise: 65K Top oil temperature rise: 60K With ambient temperature in accordance with IEC 60076-1 The temperature of the cooling air should not exceed: · 20°C yearly average · 30°C monthly average of the hottest month · 40°C at any time For other ambient temperatures, winding and oil temperature rise should be adapted
Type of cooling ONAN (Oil Natural Air Natural)
Dielectric liquid Mineral oil according to IEC or ANSI standard On request: silicon, midel, vegetal oil
Ability to withstand short-circuit The transformers are designed to withstand the thermal and the dynamic effects resulting from a secondary short-circuit in accordance to IEC 60076-5
Sound level The measurement (A-weighted sound pressure LpA) and the calculation of sound level (A-weighted sound level LwA) are done in accordance witih IEC 60076-10. The sound level requirements are in accordance with national standards.
Installations Indoor and/or outdoor
HV & LV terminals HV terminals: plug-in or porcelain bushings LV terminals: busbars or porcelain bushings On request: cable boxes according to client/manufacturer standard or norm (i.e. BS) requirements On request: protective boots for HV/LV bushings
Accessories · Standard: lifting lugs, earthing terminal name and rating plate, oil filling plug, off circuit tap changer, bi-directional rollers if applicable (out of scope hanging pole transformer) · On request: padlock/locking device for HV plig-in bushings and/or tap changer, protection relay (DGCPT2, RIS, DMCR, etc.), oil level indicator, thermometer with or without contacts pressure relief device, pressure relay with contact, oil drain plug with/without sampling device, filling valve, drain valve, explosion vent, winding temperature indicator (OTI + WTI). Accessories for conservator: dehydrating breather, buchholz relay, drain plug, oil level indicator.

RING MAIN UNITS

Full Spec Ring Main Units

Ring Main Units Full Spec

Characteristics Unit Ring Main Unit (Common values)
Rated voltage kV 12
Frequency Hz 50
Rated current (busbars) A 630
Rated Insulation Level
Power frequency withstand voltage (common value) kVrms 28
Power frequency withstand voltage (across insulating distance) kVrms 32
Lightning impulse withstand voltage – common value kVpeak 75
Lightning impulse withstand voltage – across insulating distance kVpeak 85
Short-time withstand current for main and earthing circuits kA 20
Peak withstand current for main and earthing circuits kApeak 50
Short circuit duration Sec 3
Internal arc fault classification (SF6 tank) AFL 30kA-1s
Partition class PM
Loss of Service Continuity category LSC-2A
Degree of protection for enclosure / gas tank IP54 / IP65
Rated gas pressure (at 20 degC) MPa 0.03
Minimum functional gas pressure (at 20 degC) MPa 0.02
Characteristics Unit Load Break Switch (Ring) Fuse Switch (Transformer)
Power frequency withstand voltage kVrms 28/32 35/45
Lightning impulse withstand voltage kVpeak 75/85 75/85
Rated current A 630 200
Short circuit making current kA 50 50
Switching operation class E1 E1
Mechanical endurance class M1 M1
Load breaking current A 630 na
Closed loop breaking current A 630 na
Cable charging breaking current A 10 10
Transfer current (fuse striker operation) A na 1000
Dimension
Nos. of Function (LBS/FS) Weight (kg) Width (mm) Depth (mm) Height (mm)
3 functions 400 1070 845 1650
4 functions 550 1390 845 1650
5 functions 700 1755 845 1650

FEEDER PILLAR

Full Spec Din Type LV Outdoor Feeder Pillars

Din Type LV Outdoor Feeder Pillars Full Spec

Characteristics Unit LFP800 LFP1600
Rated Voltage
Phase to Phase V 415
Phase to Neutral V 240
Rated Insulation Level
Voltage V 690
Power Frequency Withstand Voltage (1 min) kV 2.5
Rated short time current (3s) kA/3s 31.5
Normal Current Rating
Busbars A 800 1600
Incomer A 2 x 1000
Outgoing A 5 x 400 8 x 400
Material & Dimension of Busbars
Phase Busbars mm 10 x 40 (Copper) 10 x 100 (Copper)
Neutral Busbars mm 10 x 40 (Copper) 10 x 100 (Copper)
Earth Bar mm 4 x 30 (Copper)
Circuit Devices
Fuse-Switch Current A 400
Fuse-Switch Size NH2
Disconnector Current (Solid Link) A 1000
Disconnector Size NH3
Busbar Spacing mm 185
Framework
Material Electro-galvanised Steel
Thickness mm 2.5
Colour Light Grey, Blue, Red
W x D X H 1120 x 430 x 1940 1586 x 430 x 2050
Ingress Protection Rating IP33

REMOTE CONTROL BOX

Full Spec Remote Control Box (RCB)

Remote Control Box (RCB) Full Spec

Characteristics Unit Particulars
Thickness mm 2.3
Colour Light Aircraft Grey, Matte White
W x D x H mm 900 x 290 x 1050
Ingress Protection Rating IP54

PRODUCT CATALOGUES

DOWNLOAD OUR LATEST CATALOGUES HERE

Air Insulated Switchgears (AIS)

Gas Insulated Switchgears (GIS)

SF6 Ring Main Unit

Cast Resin Transformer
Oil Transformer

CERTIFICATIONS

COMPANY ISO

ISO Certificate

CIDB Certificate

MOF Certificate

JKR Certificate

SGP Certificate

ST Certificate

TNB Certificate

SESB Certificate

PRODUCTS TYPE TESTS

10D Typetest

12A20 Typetest

12A25 Typetest

24A25 Typetest

36A25 Typetest

BGA Typetest